1P AC MCB DZ47-63 C Type 230/400V~ 50HZ/60HZ Mini Circuit Breaker 3A 6A 10A 16A 20A 25A 32A 40A 50A 63A Mounting 35mm Din Rail
$11.57 – $11.99
Description
- Rated Voltage: 220V
- Type: Circuit breaker
- Is Smart Device: No
- is_customized: Yes
- Model Number: DZ47-63
- Type: Mini
- Brand Name: EARUELETRIC
- Origin: Mainland China
- Certification: CE,NONE
- Standard: IEC60947, IEC60898
- Rated Voltage: 230/400V~
- Rated current: 3A,6A,10A,16A,20A,25A,32A,40A,63A
- Mounting: 35mm din rail
- Breaking Capacity: 4KA
- Charcteristic Curve: C Type
- Place of Origin: Zhejiang, China (Mainland)
C45N series circuit breaker is used in lighting distribution system or motor distribution system for protecting overload and short-circuit in the system. The product is novel in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly and it’s installation uses with guide, it’s case and items are adopted with high fire-retartant and shockproof plastics. The product, with long life, is mainly used in AC 50Hz/60Hz, single-pole 240V or two, three, four-pole 415V circuit for overload and short-circuit protection as well as for unfrequent on-and-off switching electric equipment and lighting circuit in normal case.
GB 10963, IEC898, BS3871.1.
Specification:
No. Of pole: 1, 2, 3, 4P
Rated voltage 240V/415V AC
Rated current (C): 6, 10, 16, 20, 25, 32, 40, 50, 63A
Breaking capacity 6kA
Electrical life no less than 6000 times
Mechanical life (0-c)no less than 20000 times
Tropical trial Treatment 2(RH 95% at 5’C)
As per Instantaneous release type: C type (5ln~10ln)
Sequence |
Release |
Test |
Start state |
Tripping |
Expected |
1 |
B,C,D |
1.13In |
Cold state |
t≤1h |
Not tripping |
2 |
B,C,D |
1.45In |
Start right after |
t<1h |
Tripping |
3 |
B,C,D |
2.55In |
Cold state |
1s<t<60s |
Tripping |
4 |
B |
3In |
Cold state |
t≤0.1s |
Not tripping |
5 |
B |
5In |
Cold state |
t<0.1s |
Tripping |
Frame class |
63A |
Rated working voltage |
240V/415V |
Rated frequency |
50/60Hz |
Rated working current |
6,10,16,20,25,32,40,50,63A |
Making and breaking capacity |
6000A |
Release type |
B,C,D |
Poles |
1,2,3,4P |
Mechanical life |
20000 |
Electric life |
6000 |