Air circuit breaker tripped and reclosing failed
1. Firstly, determine whether the air circuit breaker is non accident trip
Non accident trip refers to tripping without short circuit and overload fault. There are many reasons why the air circuit breaker can not be closed. First of all, it is necessary to determine whether the trip is caused by the short circuit and overload of the circuit, or due to the fault of itself or the control circuit. The following are the steps and methods to find and determine whether it is a line fault or an air circuit breaker fault.
After it is determined that it is the fault of air circuit breaker, check it after pulling out (drawer type air circuit breaker).
2. Air Circuit Breaker Common Troubleshooting
(1) Air circuit breaker cannot be closed due to the black out to the undervoltage release
Too low voltage or power failure of the undervoltage release coil will also trip the air circuit breaker and cannot reclose. The following four situations will cause the undervoltage release coil to lose power:
The fuse of protection circuit, such as RT14, is fused, causing circuit blockage and power failure of trip coil of undervoltage tripper.
Poor contacts such as closing buttons, relay contacts, auxiliary contacts of circuit breakers, etc., and damaged components may lead to circuit blockage and power failure of trip coils.
Broken wires and loose crimping screws in the circuit will also cause the circuit to be blocked and the trip coil to be disconnected.
Because the coil of under-voltage tripper is in power-up state for a long time, environmental pollution, inflexible engagement of armature or excessive air gap between iron core and armature are easy to cause excessive current, which will cause the tripping coil to heat and burn out and lose the function of tripping coil.
The above faults can be correctly judged through observation and simple inspection and testing. Therefore, once the fault is found, it should be eliminated in time. If the contact is loose, it must be tightened, the component is damaged or the coil is burned, it needs to be replaced.
(2) Failure of mechanical system causes air circuit breaker not to close
After tripping and closing several times, the operating mechanism of air circuit breaker is severely worn and the following faults may occur:
If the motor drive mechanism is worn out, such as the worm wheel and worm of the ME switch are damaged, the operating mechanism of the air circuit breaker cannot be driven to buckle and close. The replacement of worm gears and worms is complicated and requires professional maintenance.
The wear of free tripping mechanism makes it difficult to close the air circuit breaker and easy to trip. Sometimes it just barely closes. In case of vibration, it trips itself. Sometimes once closed, it trips again.
At this time, the adjusting screw should be rotated to adjust the relative position of the tripping half shaft and the tripping so that the contact area is about 2.5mm^2. Replace the corresponding parts if necessary.
Failure of energy storage spring in operating mechanism.When closing, the four-link mechanism of the air circuit breaker can not push to the dead point and the mechanism can not self-maintain in the closing position. Therefore, the air circuit breaker can not close properly, so the energy storage spring must be replaced.
Operating mechanism is inflexible and stuck.Because this type of circuit breaker is not fully enclosed, inadvertently dropping screws, nuts and other foreign bodies in the operating mechanism will cause stuck operation of air circuit breaker, which will affect closing. In addition, lack of lubricating grease in the rotating and sliding parts will cause slight deformation of the open energy storage spring of the operating mechanism and the air circuit breaker will not close. Therefore, in addition to checking for foreign bodies in the operating mechanism, lubricating grease should be injected into the rotating and sliding parts when the above faults occur.
Structure of air circuit breaker
Press trip button, air circuit breaker refuses to break
The failure of the air circuit breaker to break normally may be due to the following failures.
1. Button failure
Mechanical failure of the button or poor contact of the conductor will cause the trip circuit to be blocked, which will lead to the deactivation of the shunt trip coil, the armature can not be pull in and the air circuit breaker can not be broken.
2. Shunt trip failure
The tripping of air circuit breaker is affected by open or short circuit of shunt trip coil and blockage of armature engagement. Therefore, regularly check the shunt trip, remove the obstacles affecting the armature attraction, and replace the coils with open or short circuit in time to ensure that the air circuit breaker can be quickly disconnected when the circuit needs to be disconnected.
3. Failure of trip-free mechanism
The contact surface between the tripping half-shaft and the tripping of the trip-free mechanism is too large (usually 2-3mm^2), which will make the circuit breaker refuse to breaking. Therefore, by using the adjusting screw, the tripping half-shaft can rotate at an angle to meet the requirements of the contact surface of 2-3mm^2, and the contact surface is coated with low temperature extreme grease to reduce friction and facilitate tripping.
Other faults
1. Noise of Undervoltage Tripper
Undervoltage tripper often produces abnormal noise after working for a period of time. Oil and dust on working surface of iron core should be removed regularly. If short circuit ring breaks, it needs to be replaced.
2. Burning out of mini-motors
Failure of the limit switch can cause the mini-motor in the electric operating mechanism to burn out. If it is necessary to close the circuit breaker with the electric operation mechanism, press the closing button, the power supply circuit of the motor will be connected, and the motor rotates. After completing the energy storage or closing of the mechanism, the power supply circuit of the micro motor should be disconnected by the limit switch. However, it cannot be disconnected due to the failure of the limit switch, which will cause the motor to overheat and burn out for a long time.
3. Short circuit due to poor insulation
The insulation performance of air circuit breaker will gradually deteriorate after long-term use. If improper maintenance is carried out in ordinary times, dust accumulation on the surface of insulating parts and moisture erosion will accelerate insulation aging, which may cause short circuit between phases or relative ground during power distribution operation or when short-circuit current is cut off.Therefore, it is necessary to keep the insulation surface clean and prevent the insulation performance from deteriorating so as to prolong the service life of the circuit breaker.
Measures required for air circuit breaker after breaking short-circuit current
After each short-circuit current cut-off, the air circuit breaker shall be checked as follows:
1. Contact system
(1) Smoke marks on the main and arc contacts are wiped off with alcohol.
(2) If small metal particles form on the contact surface, they should be cleaned and smoothed.
(3) If the thickness of silver alloy contact layer on the main contacts (dynamic and static contacts) is less than 1mm due to electric wear, it must be replaced, and the dynamic and static contacts should be replaced at the same time.
(4) Check the contact pressure spring, if it fails due to overheating, replace it in time.
(5) Check whether the flexible connection is broken or not. A few of the broken zones should be removed. If most of the zones are broken, the flexible connection should be replaced.
2. Arc Extinguishing System
(1) Clean the metal particles and soot on the wall and grids of the arc extinguishing chamber. If the grids are welded or burnt seriously, they should be replaced.
(2) If the arc extinguishing chamber is damaged, it is not allowed to be used again and must be replaced.
(3) The newly exchanged arc extinguishing chamber should be dried before use to ensure good insulation.
3. Operating mechanism and trip-free mechanism
(1) Lubricating oil can be properly filled first.
(2) Operate closing several times with electric operating mechanism and manual handle respectively. The operating mechanism should be flexible and the air circuit breaker should be closed reliably. When the switch-off button is pressed, the air circuit breaker should trip and break instantaneously.